Architecture
-
Neutral positionright
-
Number of protected poles1
-
Number of poles2 P
-
CurveC
Configuration
-
Number of modules2
Connectivity
-
Top connection alignement for modular devicesAligned terminal
Main electrical features
-
Rated short circuit breaking capacity Icn AC according IEC60898-16 kA
-
Rated operational voltage Ue240 V
-
Frequency50 Hz
Voltage
-
Rated insulation voltage500 V
-
Max operating voltage240 V
-
Rated impulse withstand voltage4000 V
Electric current
-
Rated residual operating current30 mA
-
Rated current40 A
-
Withstand not tripping on 8-20 μs wave250 A
-
Breaking and opening capacity6 kA
-
min/maxi threshold value of the AC thermal operation1.13 / 1.45 In
-
Magnetic regulating currrent5 / 10 In
-
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-16 kA
-
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-26 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-26 kA
Electric current / temperature
-
Rating current -25°C46.9 A
-
Rating current -20°C46.3 A
-
Rating current -15°C45.6 A
-
Rating current -10°C45 A
-
Rating current -5°C44.4 A
-
Rating current 0°C43.8 A
-
Rating current 5°C43.1 A
-
Rating current 10°C42.5 A
-
Rating current 15°C41.9 A
-
Rating current 20°C41.3 A
-
Rating current 25°C40.6 A
-
Rating current 30°C40 A
-
Rating current 35°C39.4 A
-
Rating current 40°C38.8 A
-
Rating current 45°C38.2 A
-
Rating current 50°C37.5 A
-
Rating current 55°C36.9 A
-
Rating current 60°C36.2 A